Pierre Pierre, who replica handbag 185cm tall, gucci replica handbags the "Diamond King" in his hermes replica handbags . He has been selected as one of the handbag replica most beautiful 50 people in the "People" magazine. It is also known as replica handbags most elegant and quiet in the world. Unforgettable prince.

NCS125-6

Data Sheet NCS125.pdf
Nominal Primary Current (Peak) 6000 A
Measuring Range (Peak) 30000 A
Secondary Current IS1 at IPN (Peak) ±20 mA
Secondary Voltage VS1 at IPN (Peak) ±10 V
Product Type Current sensors
Mounting Type Frame Mounting
Opening for Primary Conductor 165 mm
Not Measurable Overload (Peak) View 120000 A
Secondary Current IS2 at IPMAX (Peak) ±20 mA
Residual Current IS1O View = ±250 µA
Residual Current IS2O View = ±180 µA
Thermal Drift Coefficient (Outputs IS1 IS2) = ±4 µA/ºC
Measuring Resistance (Outputs IS1 IS2) 0 to 350 O
Secondary Voltage VS2 at IPMAX (Peak) ±10 V
Residual Voltage VS1O = ±100 mV
Residual Voltage VS2O = ±50 mV
Thermal Drift coefficient (Outputs VS1 VS2) = ±2 µV/ºC
Measuring Resistance (Outputs VS1 VS2) 10000 to 8 O
RMS Accuracy 50 Hz (without offset) at IPN = ±1 %
RMS Accuracy 50 Hz (without offset) at IPMAX = ±3 %
Gain Thermal Drift (-25ºC to 85ºC) = 0.03 %/ºC
Gain Thermal Drift (-40ºC to -25ºC) = 0.1 %/ºC
Linearity (Typical) ±0.5 %
Delay Time (Typical) = 3 µs
di/dt Correctly Followed = 100 A/µs
Bandwidth 0 to 10 kHz
No Load Consumption Current (IA0) = 180 mA
No Load Consumption Current (IA0-) = 35 mA
Dielectric Strength Primary/Secondary 5 kV
Supply Voltage (DC) ±15 to ±24 V
Mass 1 kg
Operating Temperature -40 to 85 ºC
Storage/Startup Temperature -50 to +90 ºC
Secondary Connection Straight connector 8 pin
Ordering Code 1SBT200604R0001
Conformity EN50178 EN61000-6-2 EN61000-6-4
Approvals CE
Features General DataPlastic case and insulating resin are self-extinguishing.Two fixing modes:Horizontal or vertical with fixing holes in the case moulding.By bar using the intermediate flange kit .Max tightening torque for M6 screws (flange mounting) : 2 N.mDirection of the Current :Output current (IS1 and IS2) : A primary current flowing in the direction of the arrow results in a positive secondary output current on terminals IS1 and IS2.Output voltage (VS1 and VS2) : A p
Details 100% electronicThe main advantage of the NCS range of sensors is that they are designed using a brand-new solution: 100% electronic technology. Unlike other currently available solutions such as shunts and CTs, this approach means that these sensors are very compact. Several patents were necessary to achieve this improvement.Considerable energy savingsNCS sensors offer considerable savings in energy. Indeed only a few watts are required to power the NCS sensor in contrast to T
  • These sensors are designed to be fixed by the case.
  • They may be either vertically or horizontally mounted.
  • The secondary connection is made with a connector or cable.
  • For NCS sensors the primary conductor may be a cable, one or several bars.